Dil ID: 1
Dil Adı: english
Dil Kodu: en3 Basco Brand's Products
Dünyanın En Büyük
Elektronik Bilgi Kütüphanesi



33333
Introducing a scalable new system for configuring versatile and highly effective PA applications. The SX-2000 Series is in compliance with the EN 54
Standard, and features new matrixing capabilities, so a single system can have its components distributed in different locations, yet under centralized
control. Ideal for large-scale installations ranging over multiple buildings as well as local systems, the versatile SX-2000 Series is particularly well-suited
for airports and railway stations, factories, shopping malls and large offices. Versatility is ensured by such features as a dual power source and redundant
backups for fail-safe operation, making it a cost-effective solution for virtually any installation, and without long lead times or the expense of a custom
system. A fireman's microphone feature is also included, for enhanced effectiveness in an emergency. SX-2000 Series components enable creation of an
ideal system for all sorts of application requirements.
Voice Evacuation Systems
2
Power Source: Usable power supply unit: VX-200PS/24V
DC (operational range: 20V – 40V DC)/Two power inputs
construction enables dual- redundant power supply.
Current Consumption: 1.1A or less (maximum value in the
power operating range)/
0.8A or less (when operated on 24V DC)
Indication/Operation: SX link access indicator: 2/LAN access
indicator: 1/Mode indicator: 3 (EMERGENCY/STANDBY/CPU
OFF)/Failure indicator: 3 (GENERAL/CPU/SX LINK)/Power
indicator: 1 (POWER)/Run indicator: 1 (RUN)/Failure control
switch: 3 (ACK/RESET/LAMP TEST)
SX Link:
Network I/F: 2 100BASE-TX circuits, RJ45 connector
Matrix System Specification: Bus: 16/Audio input: Max. 64 ch/
Audio output: Max. 128 zones/Contact input: Max. 1,416/Contact
output: Max. 1,416/Priority control: 512 steps/Event log: Up to
1,000 logs per file (up to 100 files available)/Failure log: Up to
100 logs per file (up to 100 files available)
Matrix System Configuration:
Connectable SX-2100AI No: Max. 8 units/Connectable
SX-2000AO/2100AO No.: Max. 32 units/Connectable
SX-2000CI No.: Max. 32 units//Connectable SX-2000CO No.:
Max. 32 units/Connectable RM-200SA/SF No.: Max. 64 units (up
to 4 RM-200SA per SX-2100AI)
Connection Cable/Device:
Shielded Category 5 twisted pair cable for LAN (CAT5-STP)
(Connect SX-2100AI and SX-2000AO/2100AO via the switching
hub specified by TOA)
Note: This network must be made completely independent from
other LAN.
Number of Cascaded Switching Hub: Up to 7
Maximum Cable Distance:100m (between this unit and a
Number of Switching hubs, or between Number of Cascaded
Switching Hubs)
LAN:
Network I/F: 1 10 BASE-T/100 BASE-TX circuit (selectable by
automatic recognition), RJ45 connector for maintenance use
Network Protocol: TCP/IP
Connection Cable: Shielded Category 5 twisted pair cable for
LAN (CAT5-STP)
Maximum Cable Distance: 328ft (between this unit and a
switching hub or PC)
Analog Link:
Input/Output Connector: Output: 2, RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable for
LAN (CAT5-STP) (1 pair of audio wire + 1 pair of CPU OFF + 1
pair of control wire (system reset/standby) + 1 pair of connection
check wire)
Maximum Cable Distance: Total length of analog audio link:
2625ft
DS Link:
Usable Unit: VX-2000DS
Connector/Cable: 2 interface, RJ45 Connector, Shielded
Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance: 16ft
Failure Data Input: 3 inputs (ACK/RESET/LAMP TEST),
no-voltage make contact input, open voltage: 24V DC,
short-circuit current: 2mA, photo coupler input, removable
terminal block (12 pins)
Failure Data Output: 4 outputs (CPU FAULT/GENERAL FAULT/
CPU OFF/BUZZER), C contact, no-voltage make contact output,
relay contact output (withstand voltage: 40V DC, control current:
2 – 300mA), RJ45 connector
Control Input: 8 inputs, no-voltage make contact input, open
voltage: 24V DC, short-circuit current: 2mA, photo coupler input,
removable terminal block (12 pins)
Surveillance Section for The Control Input Lines: Connection
resistance to make the function inactive: 20kΩ ±5%/Connection
resistance to make the function active: 10kΩ ±5%/Connector
cable: Twisted pair cable (shielded type is recommended)/
Maximum cable distance: 33ft
Control Output: 8 outputs, C contact, no-voltage make contact
output, relay contact output (withstand voltage: 40V DC, control
current: 2 – 300mA), removable terminal block (12 pins)
24V DC Output:
Output Voltage: 24V DC ±10% or less
Maximum Feeding Current: 100mA
Memory Card: Insertion slot: 1 (use of supplied CF card
(128MB)), set data and log data stored
Operating Temperature: 32°F to +104°F
Operating Humidity: 35% to 80% RH (no condensation)
Finish: Panel: Aluminum, black, alumite,
Case: Surface-treated steel plate
Dimensions: 19 (W)
×
1.7 (H)
×
13 (D)in
Weight: 8.4lbs
Accessory:
CD (PC setting software)
×
1, EV-CF128M (CF card)
×
1, Removable terminal plug (4 pins)
×
1, Removable terminal
plug (12 pins)
×
4, Rack mounting screw
×
4, Driver
×
1
SX-2000SM
System Manager
SX-2100AI
Audio Input Unit
Power Source: Usable power supply unit: VX-200PS/
24V DC (operational range: 20V – 40V DC)/Two power inputs
construction enables dual- redundant power supply.
Current Consumption: 2.01A or less (maximum value in the
power operating range)/
1.50A or less (when operated on 24V DC)
Note: But except current consumption of the external equipment
of which power is supplied from the unit.
Indication: 18 alphanumeric characters, Level indication (8
inputs, monitor), Status indicators, Power indicator, Standby
indicator, CPU OFF indicator
Operation: Function button, Input level control, Monitor speaker
volume control, ON/OFF switch, Operation button
Audio Input: 8 inputs, module construction (max. 4 modules,
modules optional) monitoring possible using built-in speaker.
Audio Input Characteristic: Sampling frequency: 48kHz
No. of Connectable Remote Microphone: Max. 8
Power Feed to Remote Microphone: Possible for up to a total of 8A.
SX Link:
Network I/F: 2 100BASE-TX circuits, RJ45 connector,
decentralized installation possible
Connection Cable/Device: Shielded Category 5 twisted pair
cable for LAN (CAT5-STP)
To be connected via the switching hub specified by TOA.
Note: This network must be made completely independent from
other LAN.
Maximum Cable Distance: 328ft (between this unit and a
switching hub)
Analog Link:
Input/Output Connector: Input: 1 input, RJ45 connector/
Output: 1 output, RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable for
LAN (CAT5-STP) (1 pair of audio wire + 1 pair of CPU OFF + 1
pair of control wire (system reset/standby) + 1 pair of connection
check wire)
Maximum Cable Distance: Total length of analog audio link:
2625ft
Control Input: 16 inputs, no-voltage make contact input, open
voltage: 40V DC or less, short-circuit current: 2mA, photo
coupler input, removable terminal block (16 pins)
Control Output: 16 outputs, A contact: normally open
(changeable to B contact: normally closed), no-voltage make
contact output, relay contact output (withstand voltage: 40V DC,
control current: 2 – 300mA), removable terminal block (16 pins)
Operating Temperature: 32°F to +104°F
Operating Humidity: 35% to 80% RH (no condensation)
Finish: Panel: Aluminum, black, alumite,
Case: Surface-treated steel plate
Dimensions: 19 (W)
×
3.5 (H)
×
13.7 (D)in
Weight: 16lbs
Accessory: Removable terminal plug (4 pins)
×
1, Removable
terminal plug (16 pins)
×
2, Rack mounting screw
×
4
Option: Remote microphone interface module: SX-200RM
MIC/LINE input module: D-921E, D-921F, D-922E, D-922F
Stereo input module: D-936R
Note: Modules other than described above cannot be used.
SX-2000 Series