10.0 Appendix B Configuring the IQ LAN for Version 0130 and above
10.1 Configuring the IQ LAN for Version 0130 and above
The following Configuration Instructions are for updating the IQ LAN (PCSC Part #: 03-10108-
xxx) TCP/IP Configuration.
IMPORTANT If a user is configuring the IQ LAN card for a panel addressed 112-200, the
software addressing of the panel must be configured BEFORE the IQ LAN
configuration. For more information on software addressing, see Section 7.3.2
[Software Addressing the IQ-400 Panel (Panels 112-200) Direct Connect].
10.1.1 Required Equipment:
1. PC or Notebook computer with a NIC
2. Web Browser (IE 5 or greater or Netscape 5 or greater.)
3. Ethernet Cross Over cable (example: Unicom E5DD-C414-WT-10TR) or attached to
a hub
4. IQ-400 – 03-10111-xxx
5. IQ LAN – 03-10108-xxx
10.1.2 Required Information:
1. LiNC-NET Host IP Address
2. IQ LAN IP Address – This is the unique IP Address for each IQ-400.
3. Panel Number – This is the IQ-400 panel number that the IQ LAN will be attached to.
The panel number in the IQ LAN and the IQ-400 PCB must match.
4. Any Gateway information.
10.1.3 Required firmware:
1. IQ-400 panel firmware: i4+07.010.02 or greater
2. IQ LAN version 0130 or greater