Dil ID: 1
Dil Adı: english
Dil Kodu: en5 Wintech Brand's Products
Dünyanın En Büyük
Elektronik Bilgi Kütüphanesi



8686868686
86
042-288-B0-001, Rev. A2
7.0 Maintenance, continued
7.9 Maxitrol Pre-regulator Calibration
Required Tools and Materials:
Flat Tip Screwdriver
DWYER # 1212 water column (0-16") gas pressure test kit
Allen head wrench set
NFPA-approved pipe sealant (i.e. Megaloc Multipurpose Thread Sealant)
Leak detector compound (soapy water)
The Maxitrol 325-3 regulator has a maximum inlet pressure of 10 PSI. Alpha Technologies
recommends all installations range between 1-2 PSI for consistent of gas ow.
An external water trap must be supplied outside the enclosure in accordance with local, state,
and National Fire Protection Agency (NFPA) codes. Water sent through the gas lines to the
regulator system can damage the secondary demand regulator.
Fig. 7-13, Primary Fuel Regulator
Remove cap to access
adjustment screw
CE-3x2 5K-T PN-6x-T 7.5kW