Fig. 7-10, Load Block, PN-6x-T 7.5kW
(natural gas conguration)
Fig. 7-11, Changing Load Block Conguration, PN-6x-T 7.5kW
7.0 Maintenance, continued
7.8 Fuel Conversion, Natural Gas to LP, continued
7.8.2 Switching the LP Port to the NG Port, PN-6x-T
Required Tools:
• 7/8" open-end wrench
• NFPA-approved pipe sealant
In this procedure, the gas inlet hose is switched from the LP port to the NG port.
Reverse this process if converting from natural gas to liquid propane.
1. Loosen swivel connector and remove from are tting.
2. Turning counterclockwise, remove are tting and plug from unused port.
3. Coat all but last two threads of the are tting and plug.
4. Reinstall are tting and plug into the opposite holes, reconnect hose.
5. Set the selector switch on the Gas Hazard Sensor to the correct setting.
6. Apply gas pressure and test all ttings for leaks with test solution or soapy water.
The following procedure must only be performed by qualied personnel. To prevent
injury, disable generator and disconnect gas supply prior to beginning the gas conversion
procedure.
WARNING!