OPERATING INSTRUCTIONS
30 4
012/16 Diesel, February 1997
NORMAL STARTING PROCEDURE
WHEN FITTED WITH THE
REGULATEURS EUROPA 2100
GOVERNOR AND A WOODWARD TYPE
UG10 OR 3161
Ensure that where possible the load is off.
Set the engine switch to the 'run' position and
press the starter button, the engine should
start immediately and run up to full speed.
If the engine does not start within a few
seconds, do not keep the starter engaged,
let the engine come to rest and begin again.
Allow 15 seconds between start attempts. If
the engine fails to start after several
attempts, do not persist in motoring the
engine but investigate the cause. Check oil
pressure, for fuel and oil leaks and that the
ammeter in the instrument panel is showing
charge to the engine batteries. Allow the
engine to run for 5 minutes. Check
instruments are reading correctly. Apply
load.
NORMAL STARTING PROCEDURE
WHEN FITTED WITH THE HEINZMANN
E16 AND WOODWARD PROACT II
ELECTRONIC GOVERNOR
Operate the start control, which will energise
the solenoid and allow the governor lever to
move to the 'run' position Fig. 11, the engine
should then start immediately. Again check
the oil pressure, for any fuel or oil leaks, and
that the ammeter in the instrument panel is
showing charge to the engine batteries.
Allow the engine to run for five minutes,
checking that instruments are reading
correctly. Apply load.