NO. ITEM NO.
1 — Pressure Gage 12 —
2 — Purge Separator Assembly
3 — Refrigerant (Vapor) In 13 —
4 — Tube-in-Tube Condenser 14 —
5 — Filter Drier Vi SAE Flare (Hidden)
6 — Refrigerant (Liquid) Out
7 — Oil Separator
8 — Pump
9 — Pump Motor
10 — Heater High-Pressure
Cutout Switch (Hidden)
11 — Heater ON/OFF Switch (Hidden) 15 —
ITEM
Pump High-Pressure
Cutout Switch
Pump ON/OFF Switch
Storage Area
Components Included:
Refrigerant Hose, 3 ft
Refrigerant Hose, 6 ft (2)
Refrigerant Hose, 12 ft
Valve With Coupler (8)
Chiller Vapor Valve
Liquid Indicator With Coupler
Vapor Valve
NO. ITEM
16 — Refrigerant Capacity Chart
17 — Relief Valve Assembly
18 — Level Gage
19 — Liquid Valve
20 — Accessory Casters
(Available On All Tank Sizes)
21 — Water Separation Sight Glass
22 — Heater With Cover
23 — Storage Tank
24 — Water In
25 — Water Out
Fig. 4 — 19QA Refrigerant Management System Components
Table 3 — Electrical Data
Fig. 5 — Interconnecting Refrigerant Hoses,
Valves, and Fittings
VOLTS-PH-HZ 115-1-50
115-1-60 230-1-50
230-1-60
PUMP MOTOR
Hp 3/4
3/4
3/4 3/4
Amps 9.6 8.6 4.8 4.3
MCA
10
10
5 5
HEATER
Amps
12 12 6
6
MCA 12 12 11 11
MOCP 15* 15*
15
15
LEGEND
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (Amps)
*Two circuits required for simultaneous operation.
NOTE: Use time-delay fuses.