60 Rockwell Automation Publication 440R-UM009B-EN-P - February 2014
Appendix D Tag Definitions
Table 12 - GSR GLP NonRecoverableFault_A and NonRecoverableFault_B Fault Codes
Fault
Code
Description Corrective Action
00H No fault None
03H Jitter fault
04H Proximity Sensor 1 (P12) stuck at High
fault: Potential damage or
misalignment of the Proximity Sensor
(e.g. exceeding maximum sensing
distance, both sensors detecting a
space).
Do one of the following:
Check the alignment and functionality of the Proximity
Sensor.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
http://rockwellautomation.com/support
04H Proximity Sensor 2 (P22) stuck at High
fault.
06H Proximity Sensors cross fault. Do one of the following:
Check connection of P12 and P22 against shorts to 24V or
0V and cross loop shorts.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
http://rockwellautomation.com/support
07H Self test of terminal 51 failed. Do one of the following:
Check connection of 51 or L61 against shorts to 24V or 0V
and cross loop shorts.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
http://rockwellautomation.com/support
08H Self test of terminal L61 failed.
09H Proximity Input Fault: Both Proximity
inputs are Low simultaneously.
Do one of the following:
Check the alignment and functionality of the Proximity
Sensors.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
http://rockwellautomation.com/support
0AH Proximity Input Fault: Both Proximity
inputs stuck at HIGH simultaneously.
0BH SPI compare fault
0CH Self test of Single Wire Safety outputs
L11, L61 fault
Do one of the following:
Check connection of L11 or L61 against shorts to 24V or 0V
and cross loop shorts.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
http://rockwellautomation.com/support
0DH Current configuration does not agree
with the safety relay memory:
Switch settings do not match
required initial configuration or
X14 and X24 are connected to inputs
S12, S22 but they are configured as
safety outputs or
L1 and 51 connection has changed
after configuration
Do one of the following:
Change the switch settings to the correct values.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
http://rockwellautomation.com/support