Rockwell Automation Publication 193-UM012B-EN-P - June 2011 85
Appendix B
The following services are implemented for the Assembly Object:
Connection Manager Object — CLASS CODE 0x06
No class or instance attributes are supported.
The following common service are implemented for the Connection Manager
Object:
Discrete Input Point Object — CLASS CODE 0x08
The following class attributes are supported for the Discrete Input Point Object:
16 Trip Log 2 (low byte)
17 Trip Log 2 (high byte)
18 Trip Log 3 (low byte)
19 Trip Log 3 (high byte)
20 Trip Log 4 (low byte)
21 Trip Log 4 (high byte)
Table 23 - EtherNet Object Common Services
Service
Code
Implemented for: Service Name
Class Instance
Consuming
Instance
Producing
0x0E Yes Yes Yes Get Attribute Single
0x10 No Yes No Set Attribute Single
Table 24 - Connection Manager Object Common Services
Service Code Implemented for: Service Name
Class Instance
0x54 No Yes Forward Open
0x4E No Yes Forward Close
Table 25 - Discrete Input Point Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0002
2 Get Max Instance UINT 0x0002
Table 22 - Instance 111 —Complete Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0