84 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
Input Assemblies
Table 18 - Instance 50 — Trip Status Input Assembly from ODVA Overload Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Tripped
Table 19 - Instance 51 —Basic Status Input Assembly from ODVA Overload Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Warning Tripped
Table 20 - Instance 106 —Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Motor
Current
Input 2 Input 1 Out A Stat Warning Tripped
Table 21 - Instance 110 —Extended Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Motor
Current
Input 2 Input 1 Out A Stat Warning Tripped
1Unused
2 Average % FLA (low byte)
3 Average % FLA (high byte)
4 %Therm Utilized (low byte)
5 %Therm Utilized (high byte)
Table 22 - Instance 111 —Complete Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Motor
Current
Input 2 Input 1 Out A Stat Warning Tripped
1Unused
2 Average % FLA (low byte)
3 Average % FLA (high byte)
4 %Therm Utilized (low byte)
5 %Therm Utilized (high byte)
6 Trip Status (low byte)
7 Trip Status (high byte)
8 Warning Status (low byte)
9 Warning Status (high byte)
10 Device Status (low byte)
11 Device Status (high byte)
12 Trip Log 0 (low byte)
13 Trip Log 0 (high byte)
14 Trip Log 1 (low byte)
15 Trip Log 1 (high byte)