Dil ID: 1
Dil Adı: english
Dil Kodu: en3 Boston Whaler Brand's Products
Dünyanın En Büyük
Elektronik Bilgi Kütüphanesi



4343434343

A–3


PWM Algorithm Sine Weighted PWM with Harmonic Compensation
Switching Device (3-Phase Output)
IGBT (Intelligent Power Module)
V/Hz Ratio Programmable
Carrier Frequency
Adjustable from 2kHz to 8kHz in 100 Hz Increments (Factory default is 4 kHz)
DC Boost Adjustable - Select from a family of Boost Curves
Current Limiting
T
rip Free Operation, CoĆordinated for Controller and Motor Protection - Programmable from
20% to 190% of Controller Output Current
Motor Protection I
2
t Overload Protection - 150% for 60 seconds, 200% for 30 seconds
Overload Pattern #0
Flat response over speed range (no speed compensation)
Overload Pattern #1
Speed compensation below 25% of Base Speed
Overload Pattern #2 Speed compensation below 100% of Base Speed
Acceleration/Deceleration Time(s)
0.1 to 600 Seconds
S-Curve Accel/Decel Time(s) 0 to 100% of Accel/Decel time - not to exceed 60 seconds
Stopping Modes
3 modes (programmable)
Ramp to stop 0.1 to 600 seconds
Coast Stops all PWM Output
DC Brake to stop
Applies DC V
oltage to the Motor for 0 to 15 seconds

Overcurrent
200% hardware limit, 300% instantaneous fault
Excessive Temperature Embedded temperature sensor trips if heatsink temperature exceeds 95°C
Over/Under V
oltage DC Bus voltage is monitored for safe operation.
For controllers rated at input voltage 200-240 V
AC, overvoltage trip occurs at 410 VDC bus
voltage (equivalent to 290 V
AC incoming line voltage).
For controllers rated at input voltage 380-460 V
AC, overvoltage trip occurs at 815 VDC bus
voltage (equivalent to 575 V
AC incoming line voltage ).
For controllers rated at input voltage 200-240 V
AC, undervoltage trip occurs at 210 VDC bus
voltage (equivalent to 150 V
AC incoming line voltage).
For controllers rated at input voltage 380-460 V
AC, undervoltage trip occurs at 390 VDC bus
voltage (equivalent to 275 V
AC incoming line voltage).
Control Ride Through
Minimum ride through is 0.5 seconds - typical value 2 seconds
Ground Short
Any output short to ground, detected prior to start
Faultless Ride Through
100 Milliseconds
Output Short Circuit Any output phase to phase short
   
Programmer
Optional, Removable Program Keypad Module
Type of Display
6 character LED - two digit parameter number and four digit value
Local Controls SPEED, RUN, STOP, and DIRECTION controls