6 Rockwell Automation Publication PFLEX-IN020C-EN-P - July 2013
PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures
Power Structure Weights and Lifting Instructions
Use the weights listed in the tables below and the Lifting Instructions on page 8
when lifting the power structures.
Table 3 - Frames 10…12 Approximate Weights
ATTENTION: To guard against possible personal injury and/or equipment
damage...
• Remove any wiring access covers at the top of the drive.
• Do Not allow any part of the drive or lifting mechanism to make contact with
electrically charged conductors or components.
• At no time should a person or their limbs be directly underneath the items
being lifted.
• Do not subject the load to high rates of acceleration or deceleration.
• Inspect all lifting hardware for proper attachment before lifting drive unit.
Frame
Size
Drive
Voltage
Class
Drive
Rated
Amps
Power Structure Weight AC Choke Weight AC Input Drive and
Packaging Weight
(4)
(4) DC input drive and packaging weight is equal to the weight of the power structure(s).
kg (lb) kg (lb) kg (lb)
10 400 385 120 (265) 115 (254) 235 (519)
460 120 (265) 115 (254) 235 (519)
500 120 (265) 115 (254) 235 (519)
600 261 120 (265) 53 (117) 173 (382)
325 120 (265) 84 (185) 204 (450)
385 120 (265) 84 (185) 204 (450)
416 120 (265) 84 (185) 204 (450)
11 400 590 210 (463) 84 (185)
(2)
(2) Two AC chokes are required for this frame 11 AC drive.
378 (833)
650 210 (463) 84 (185)
(2)
378 (833)
730 210 (463) 84 (185)
(2)
378 (833)
600 460 210 (463) 115 (254) 325 (717)
502 210 (463) 115 (254) 325 (717)
590 210 (463) 115 (254)
(2)
440 (970)
12 400 820 120 (265)
(1)
(1) Two power structures are required per frame 12 drive.
115 (254)
(3)
(3) Two AC chokes are required per frame 12 AC drive.
350 (772)
920 120 (265)
(1)
115 (254)
(3)
350 (772)
1030 120 (265)
(1)
115 (254)
(3)
350 (772)
600 650 120 (265)
(1)
84 (185)
(3)
288 (635)
750 120 (265)
(1)
84 (185)
(3)
288 (635)
820 120 (265)
(1)
84 (185)
(3)
288 (635)