2. Pre-Installation
2.3 Enclosure Grounding
Lightning Protection (Optional)
1/2" x 8' copper ground rod, four places, driven about 2 feet (typical) from the corners of the pad.
#2 bare copper wire loop terminated to each ground rod and buried below grade 2 to 12 inches.
Corrosion-proof connections (25+ year life-span) and hardware suitable for direct burial MUST be used
#2 bare copper wire from loop to the enclosure
When the electrical supply is a primary service (not a secondary or feeder service) a #2 bare copper wire
must be bond the lightning protection loop to the Grounding Electrode Conductor where they are closest.
Service Grounding (required)
#6 bare copper wire from Service Neutral / Ground Bar with 2 ground rods located 6' apart.
3
2
1
4
5
Opening for
Sweeps
Opening for
Sweeps
Enclosure Footprint
2 feet
(
min)
TWO (2) 8GROUND
RODS
PLACED A MINIMUM
OF
6’ APART
#2 AWG
#6 AWG
Opening for
Sweeps
1
4
5
2
3