3.0 Operation Using the Line Transfer Switch (LTS), continued
3.2 Operation
1. Refer to the generator's operation manual and start the generator.
2. Check operation of the power supply. Ensure input current to the power supply does not
exceed the generator's rating.
• Kipor (IG2000)= 12A (derated @ 1400W)
• Honda (EU2000i) = 13.3A (rated @ 1600W)
3. When proper operation is verifi ed, close the PWE and GEM enclosures.
CAUTION!
The Alpha XM2 power can draw an additional 400W during battery charging operation. If the
combined load exceeds the generator's listed rating, turn the power supply DC breaker OFF to
avoid an over current condition.
NOTE:
Turning off the DC breaker while the power supply is in inverter mode will cause the load to be dropped.
Ensure the power supply is in normal operation before turning off the battery breaker