Dil ID: 1
Dil Adı: english
Dil Kodu: en5 Weatherables Brand's Products
Dünyanın En Büyük
Elektronik Bilgi Kütüphanesi



55555
TPS3 09 Installation Instructions
Pre-Plan your installation. You need to accomplish the following:
Meet all National and Local codes (NEC
®
Article 285 and UL
1449 address SPDs)
Confirm System voltage to SPD voltage (120V SPD will fail
instantly on 240V, 277V, etc.)
Mount SPD as close to panel or equipment as possible to keep
leads short (long leads hurt performance substantially)
Ensure leads are as short and straight as possible, including
neutral and ground. If using a breaker, use a breaker position
that is close to the SPD and the panel’s neutral & ground
If using a breaker, recommended breaker size is 30A due to
10 AWG conductor
Make sure system is grounded per NEC
®
and clear of faults
before energizing SPD (inadvertent system problem may fail
SPD).
Never Hi-Pot test Any SPD (will prematurely fail SPD)
Do not install the TPS3 09 through the bottom of a NEMA
3R panel. Dripping water will prematurely fail the SPD.
1. Use voltmeter to check voltages and ensure correct SPD. See Data
Sheet for specs & wire-outs
2. Determine Mounting location weather resistant equipment
may be required
3. If SPD has optional Dry Contact and Flush Mount Kit, pre-plan
their installation. See Figures 4&6. (If flush mounting, be careful
to not drop SPD into wall)
4. Remove power from panel/source. Confirm panel/source is
deenergized.
5. Identify breaker location and SPD location. Position SPD such that
LEDs are best visible.
6. Mount SPD weather resistant applications require additional
sealing, o-rings, etc. (not included)
- Remove an appropriately sized knockout from panel.
- Connect conductors as appropriate short and straight as possible
(Hi-Legs are Phase B)
- Note that the metallic connection hub is not grounded within the SPD
and proper grounding requires connection of the green conductor
ground.
7. Label or mark conductors as appropriate (neutral: white, ground:
green, energized: black, hi-leg: orange)
8. Make sure system is bonded per NEC
®
and is clear of hazards or
faults before energizing (N-G bonding not per NEC
®
will fail SPDs:
#1 cause of SPD failures)
9. Energize and confirm proper operation of green LED indicators
and/or options.
A
B C
GN
BREAKER
Use closest breaker to SPD
Locate SPD close to intended
breaker
Keep Leads Short as Possible
Avoid Sharp Bends
Figure 4: Typical Flush Mount Installation
Phase, Ground,
and Neutral Wires
SPD
Mounting Screws
(4 places, through mountingplate into mounting
surface, screws not provided)
Flush Mount Kit Screws
(8-32 x 5/8Thread Cutting, 4 places, through
plate into SPD)
Mounting Surface
Removed Material
Flush Mount Plate
Figure 5: Lead Lengths
Leads: Short & Straight
Cut Excess; Do Not Coil or Loop
CUT OFF EXCESS
LENGTH
DO NOT LOOP OR
COIL
SHORT &
STRAIGHT
X
Not
Good
p
Good
CONDUCTING DIELECTRIC AND/OR
HI-POTENTIAL TESTING WILL CAUSE
INTERNAL DAMAGE TO TPS3 UNIT.
Do not perform dielectric or high potential
tests with the TPS3 unit installed.
CAUTION
V
Hazardous voltage.
Will cause death or serious injury.
Keep Out.
Qualied personnel only.
Disconnect and lock off all power before
working on this equipment.
V DANGER