- 18 -
high or not
cooling and
running
continually
seal
b. Cabinet too large
c. Ambient temperature too high
d. Exhaust restricted
e. Malfunctioning fans
f. Evaporator or condenser airflow
g. Dirty Condenser
h. Iced evaporator
i. Refrigeration system restriction
j. Refrigerant leak
k. Undercharge or overcharge
l. Failed components
opening
b. Check for excessive size
c. Check installation location
d. Leave minimum clearance for the
hot air exhaust and fresh air intake
sides
e. Check for both evaporator and
condenser fans
f. Check for air restrictions, air short-
circulation, grille directions
g. Clean condenser
h. Defrost and reset temperature
i. Call service
j. Call service
k. Call service
l. Check compressor windings, start
relay and overload protector
7. Unit running
too long
a. Improper cabinet insulation &
seal
b. Exhaust restricted
c. Cabinet too large
d. Ambient temperature higher >
90
°F
e. Dirty Condenser
f. Improper condenser air flow
a. Check insulation, gasket and door
opening
b. Leave minimum clearance for the
hot air exhaust and fresh air intake
sides
c. Check for excessive size
d. Check for installation location
e. Clean condenser
f. Check for fan and air short
circulation
8. Fan motor
running but
compressor
not running
a. Post-compressor fan running
mode
b. Incorrect or loose wirings
c. Failed components
d. Liquid refrigerant in the
compressor
a. Check fan running time FON
b. Check all wirings and connections
c. Check start relay, start capacitor,
overload protector, compressor.
d. Call service.
9. Compressor
running but
fan not
running
a. Fan blade stuck
b. Incorrect or loose wirings
c. Failed motors
a. Check for proper clearance
b. Check all wirings
c. Call service
10.Temperature
high,
compressor
stopping
and starting
but very
short
running time
a. Failed components
b. Improper condenser airflow
c. Dirty condenser
d. Overcharge of refrigerant
e. Discharge or suction pressure
too high
a. Check compressor windings, start
relay and overload protector.
b. Check for condenser fan
c. Clean condenser
d. Call service for removing refrigerant
e. Call service for information
11.Fan running
too long
a. Post-compressor fan running
mode for humidity modulation
a. Reset FON
12.Temperature
low
a. Low temperature setting
b. Low ambient temperature
c. Air probe fault
a. Raise the setting
b. Move to another location
c. Change a new one