Abmessungen / Dimensions
Gewicht – Weight (Kg) 27.7 27.7 30 39.7
Schutzart innen/aussen / Protection rating int. /ext.
Kühlleistung / Cooling performance (DIN 3168)
Kältemittel / Refrigerant
Max. Betriebsdruck / Max. working pressure
Nennspannung / Netzfrequenz / Voltage / Frequency
230V
50/60Hz
120V
60Hz
230V
50/60Hz
120V
60Hz
400V
2~
460V
2~
230V
50/60Hz
120V
60Hz
400V
2~
460V
2~
230V
50/60Hz
120V
60Hz
400V
2~
460V
2~
230V
50/60Hz
120V
60Hz
400V
2~
460V
2~
Nennstrom / Rated current (A) 2.8 5.4 2.5 5.3 1.6 1.4 3.8 6.4 2.4 2.1 3.2 6.7 2 1.8 5.1 9.6 2.6 2.9
Max. Anlaufstrom (A) Max. start-up current (A) 6.1 12.5 9.8 19.1 4.3 4.3 10.1 20.5 4.5 4.5 15.9 30.2 5.1 5.1 21.2 39.4 5.3 5.3
Sicherung – Fuse rating (T) 6 A 10 A 6 A 10 A 2x3.6 A 2x3.6 A 6 A 16 A 2x3.6 A 2x3.6 A 10 A 16 A 2x3.6 A 2x3.6 A 10 A 16 A 2x6 A 2x6 A
Nennleistung (W) Power consumption (W) 335 275 370 440 410 410 410 540 450 450 550 700 600 700 800 880 880 1,000
Umgebungskreislauf / Ambient air circuit
Schrankkreislauf / Cabinet air circuit
Zertifizierung / Certifications
R134a
PS35 / PO30 bar
410 m
3
/h
300 m
3
/h
CE
43083XXX
650 x 315 x 260 mm
33.7
IP 54 / IP 24
750 W (L35L35)
CE
43053XXX
650 x 315 x 260 mm
33.7
IP 54 / IP 24
550 W (L35L35)
R134a
PS35 / PO30 bar
410 m
3
/h
300 m
3
/h
CE
PS35 / PO30 bar
Elektrische Anschlussdaten / Electrical data
Max. Luftvolumenstrom / Air volume flow
90 m
3
/h
115 m
3
/h
500 x 280 x 200 mm
27.7
IP 54 / IP 24
320 W (L35L35)
R134a
43103XXX
43153XXX
PS35 / PO30 bar
R134a
IP 54 / IP 24 IP 54 / IP 24
650 x 315 x 260 mm
36 47.7
980 x 395 x 260 mm
1 kW (L35L35) 1.5 kW (L35L35)
R134a
470 m
3
/h
410 m
3
/h
300 m
3
/h
PS35 / PO30 bar
CE CE
600 m
3
/h
Controller
The unit is equipped with a temperature controller which regulates the funcon of
the refrigeraon cycle. On normal working condion the display shows the tempera-
ture inside the enclosure. The controller “set point” for the interior of the enclosure
(parameter St) is set at 35
o
C from factory and can be adjusted between +20
o
C and
+50
o
C.
The High temperature alarm (parameter AH) is preset at 55
o
C.
The High Temperature Alarm relay is delivered as “normally closed” (H1=1). If you
need to change it to “normally open”, please modify value of parameter H1 (H1=2).
To modify controller parameters:
1. Press the SET buon for more than 3 sec. (if there are acve alarms, mute the buzz-
er). The display shows the parameter code ‘PS’ (password);
2. Only for parameters requiring password: Press the SET buon to access the pass-
word seng, use the UP and DOWN buons to scroll the numbers unl displaying,
“22” (default password to access the parameters), press the SET buon to conrm the
password
3. Use the UP and DOWN buons to scroll the parameters. The LED
corresponding to the category of parameters will be on
4. Press SET to display the value associated with the parameter
5. Increase or decrease the value using the UP or DOWN buon respecvely
6. Press SET to temporarily save the new value
7. Press the SET buon for more than 3 sec. to permanently save the new parameters
and exit the parameter seng procedure.
If no buon is pressed for 60 sec. all changes made to the parameters, temporarily
saved in the RAM, will be cancelled and the previous sengs restored. The cooling
unit manufacturer is in no way liable for any alteraons the customer may make to
the factory set parameters, unless the manufacturer has authorized the customer in
wring to change them.
This manual is intended as quick reference for controller, for a full controller man-
ual or if you need to restore the factory parameters please logon to our website
www.seifertsystems.com to download the full manual or to locate your nearest
servicing oce.
Door Switch:
The unit can be switched on and o via a door contact switch (terminals T1 & T2).
When delivered the door contact terminals are bridged on the female connector. To
connect the door contact switch remove the bridge and connect door contact switch.
The contact must be closed when the cabinet door is closed.
EN
Steuerung
Das Kühlgerät ist mit einer Temperatursteuerung ausgestaet welche die Funkonen
des Kältekreislaufs regelt. Der Steuerungssollwert für die Schaltschrankinnentem-
peratur (Parameter St) ist werkseitg auf +35
o
C voreingestellt, kann aber wahlweise
auf Werte zwischen +20
o
C und +50
o
C geändert werden. Der Alarmwert für zu hohe
Temperatur (Parameter AH) ist werkseig auf 55
o
C eingestellt.
Das Relais für den Alarm zu hohe Temperatur ist werkseig auf “ normal geschlossen”
(H1=1) eingestellt. Wenn Sie auf “normal oen” wechseln möchten, ändern Sie bie
H1 auf H1=2.
Zugri auf die Parameter:
• Die SET-Taste für länger als 3 Sek. gedrückt halten (im Alarmfall den Summer abstel-
len). Auf dem Display erscheint der Code des Parameters “PS” (Passwort).
• Die Parameter mit den UP- und DOWN-Tasten ablaufen. Auf dem Display erscheint
die LED der jeweilgen Parameterkategorie.
• Die SET-Taste drücken, um den zugehörigen Wert anzuzeigen.
• Den Wert mit den UP- und DOWN-Tasten erhöhen oder vermindern.
• Mit SET den neuen Wert vorübergehend speichern und zur Parameterebene zurück-
kehren.
• Das Verfahren für die anderen, zu ändernden Parameter wiederholen.
• Die SET-Taste für länger als 3 Sek. drücken, um die Parameter endgülg zu
speichern und das Änderungsverfahren zu verlassen.
Wird für 60 Sek. keine Taste gedrückt, werden alle Parameteränderungen, die
vorübergehend im RAM gespeichert sind, annulliert und die vorhergehenden Einstel-
lungen werden wiederhergestellt.
Der Hersteller des Kühlgerätes ist in keinem Fall für Änderungen die der Kunde an
den werkseigen Einstellungen vollzogen hat verantwortlich, es sei denn er hat den
Kunden hierzu vorher schrilich authorisiert.
Diese Kurzanleitung zum Bedienen der Steuerung dient nur als Referenz. Um das
komplee Handbuch für die Steuerung herunterzuladen, oder die Werkeinstellungen
wiederherzustellen, gehen Sie bie auf unsere Webseite www.seifertsystems.com
oder kontakeren Sie einen unserer Servicepartner.
Türschalter:
Das Kühlgerät kann miels eines Türkontaktes ein- und ausgeschaltet werden
(Klemmen T1 & T2). Werkseig sind diese Klemmen überbrückt. Um den Türkontakt
anzuschliessen enernen Sie bie die Brücke. Der Kontakt muss geschlossen sein
wenn die Türe zu ist.
DE