Technical details
Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02
39
Environmental data 311602
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C
Condensation Not permitted
EMC EN 61131-2
Vibration
In accordance with the standard EN 60068-2-6
Frequency 5,0 - 150,0 Hz
Max. acceleration 1g
Shock stress
In accordance with the standard EN 60068-2-27
Acceleration 15g
Duration 11 ms
Max. operating height above sea level 2000 m
Airgap creepage
In accordance with the standard EN 61131-2
Overvoltage category II
Protection type
In accordance with the standard EN 60529
Mounting (e.g. cabinet) IP54
Housing IP20
Terminals IP20
Potential isolation 311602
Potential isolation between CANopen and system voltage
Type of potential isolation Functional insulation
Rated surge voltage 500 V
Potential isolation between MODBUS and system voltage
Type of potential isolation Functional insulation
Rated surge voltage 500 V
Mechanical data 311602
DIN rail
Top hat rail 35 x 7,5 EN 50022
Material
Bottom PC
Front PC
Cross section of external conductors with screw ter-
minals
1 core flexible 0,25 - 2,50 mm², 24 - 12 AWG
2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve
0,20 - 1,50 mm², 24 - 16 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors
0,20 - 1,50 mm², 24 - 16 AWG
Torque setting with screw terminals 0,50 Nm
Connection type Spring-loaded terminal, plug in; Screw terminal,
plug in
Cross section of external conductors with spring-load-
ed terminals: flexible with/without crimp connector
0,20 - 2,50 mm², 24 - 12 AWG