I/O Modules
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Dry Contact and Mechanical Relay Output Modules
Type/Function Grayhill Part Number
Miniature, Normally Open 70M-ODC5R 70M-ODC24R
Standard, Normally Open 70-ODC5R 70-OAC5RLY 70-ODC24R
Specifications Units
Maximum Line Voltage Vdc/Vac 100/120 110/250 100/120
Load Voltage Range Vdc/Vac 0-100/0-120 0-110/0-250 0-100/0-120
MaximumContactRating W 10 90 10
MaximumSwitchingCurrent
1
A 0.5 3.0 0.5
Maximum Carry Current
1
A 1.0 5.0 1.0
Minimum Life Expectancy
@ 10 Vdc/10 mA Cycles 200 x 10
6
— 200 x 10
6
@ 48 Vdc/100 mA Cycles 500 x 10
3
— 500 x 10
3
@ 120 Vac/80 mA Cycles 500 x 10
3
— 500 x 10
3
@ 30 Vdc or 230 Vac/3A Cycles — 100 x 10
3
—
Maximum Contact Resistance
3
mW 250 250 250
Maximum Off-State Leakage mA .002 .002 .002
Maximum Turn-On Time
2
mSec 1 11 1
Maximum Turn-Off Time
2
mSec 1 11 1
Nominal Logic Voltage (Vcc) Vdc 5 5 24
Logic Voltage Range Vdc 4.8-6.0 4.8-6.0 20-30
Maximum Logic Supply Current
@ Nominal Vcc mA 10 30 20
NominalInputResistance(Rx) W 500 200 1700
Minimum Drop-Out Voltage Vdc 2.5 4.8 23
Maximum Reverse Logic Voltage Vdc -5 -5 -5
Standard and Miniature Modules
SPECIFICATIONS BY PART NUMBER
(all specs at 25
o
Cunlessnotedotherwise)
G5 and OpenLine
®
Modules
Type/Function Grayhill Part Number
G5 Fusible, Normally Open 70L-ODC5R 70G-ODC5R 70G-OAC5RLY 70G-ODC24R
Specifications Units
Maximum Line Voltage Vdc/Vac 200/200 100/120 110/250 100/120
Load Voltage Range Vdc/Vac 0-200/0-200 0-100/0-120 0-110/0-250 0-100/0-120
MaximumContactRating W 10 10 90 10
MaximumSwitchingCurrent
1
A 0.5 0.5 3.0 0.5
Maximum Carry Current
1
A 1.5 1.0 5.0 1.0
Minimum Life Expectancy
@ 1Vdc/10 mA Cycles 1000 x 10
6
— — —
@ 10 Vdc/10 mA Cycles — 200 x 10
6
— 200 x 10
6
@ 48 Vdc/100 mA Cycles — 500 x 10
3
— 500 x 10
3
@ 120 Vac/80 mA Cycles 500 x 10
3
500 x 10
3
— 500 x 10
3
@ 30 Vdc or 230 Vac/3A Cycles — 100 x 10
3
—
Maximum Contact Resistance
3
mW 300 250 250 250
Maximum Turn-On Time
2
mSec 1 1 11 1
Maximum Turn-Off Time
2
mSec 1 1 11 1
Max. Off-State Leakage @ Max. Line mA .002 .002 .002 .002
Nominal Logic Voltage (Vcc) Vdc 5 5 5 24
Logic Voltage Range Vdc 4.5-6.0 4.8-6.0 4.8-6.0 18-30
Max. Logic Supply Current
@ Nominal Vcc mA 30 max./channel 10 30 30
NominalInputResistance(Rx) W 167 500 200 1200
Minimum Drop-Out Voltage Vdc 4.5 1 1 23
1
InductiveloadsrequirediodesuppressionorRCnetwork
2
Times include debounce
3
Initial value
Available from your local Grayhill Distributor.
Forpricesanddiscounts,contactalocalSalesOfce,
an authorized local Distributor or Grayhill.