20
If national standards are not in effect, follow these guidelines to ground
the sensor and remote booster amplifier via the provided ground screws:
• Use copper wire, 14 AWG (2,5 mm²) or larger wire size, for
grounding.
• Keep ground leads as short as possible.
• Use less than 1 ohm impedance for ground leads.
• Connect ground leads directly to earth, or follow plant guidelines.
For instructions on grounding the transmitter, see the transmitter Quick
Reference Guide.