Dil ID: 8
Dil Adı: italy
Dil Kodu: it10tayfun Prodotti del Marchio BT
Dünyanın En Büyük
Elektronik Bilgi Kütüphanesi



IM-P405-39 AB Issue 4
47
10.10 Default settings
10.10.1 MODE MENU
Allows the valve to be manually opened or closed, automatically opened and closed
under the control of the timer
Ranges AUTO, OPEN, OFF
Default AUTO
10.10.2 DATA MENU
TEMP (temperature units)
Ranges °C or °F
Default °C
PRIORITY
Ranges 0 - 9 (Highest priority)
Default 0 (Timer not linked)
Resolution (steps) 1
10.10.3 RECOVERY (flash vessel cooling time - after previous blowdown)
HRS - HOURS
Ranges 00 - 11
Default 4
Resolution (steps) 1
Units Hours (HRS)
MINS - MINUTES
Ranges 00 - 59
Default 00
Resolution (steps) 1
Units Minutes (MIN)
10.10.4 INPUT MENU
SWITCH (if a switch is fitted to the valve, select fitted)
Ranges FITTED or NONE
Default NONE
CLOSING (time allowed for valve to close) - Only available if a switch is fitted
Ranges 0 - 10
Default 5
Resolution (steps) 1
Units Seconds
LIFT (time allowed for valve to lift of the seat) - Only available if a switch is fitted
Ranges 0 - 10
Default 5
Resolution (steps) 1
Units Seconds