Quick start
VEGAPULS SR 68 • Probus PA
38296-EN-130624
Quick start
The quick start procedure enables a quick setup with many applica-
tions. You can nd further information in the respective chapters of the
operating instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should
protrude > 10 mm into the vessel
ca. 10 mm
200 mm
(7.87
")
Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling
2. Note min. socket diameter depending on the socket length
3. Note the instructions for sealing
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specica-
tions on the type label.
2. Connect the instrument according to the following illustration
5
00
5
1
6
2
7
3
8
4
9
0
5
1
6
2
7
3
8
4
9
1
0
1
678
Bus
2
3
4
5
1
2
+
( )
(-)
1
Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 Selection switch for bus address
4 For external display and adjustment unit
5 Ground terminal for connection of the cable screen
For further information see chapter "Connecting to power supply".
1. Go via the display and adjustment module to the menu "Setup".
2. Select in the menu item "Medium" the medium of your applica-
tion, for example "Powder/Dust".
Mounting
Electrical connection
Set parameters