Quick start
VEGAPULS 66 enamel • 4 … 20 mA/HART - four-wire
36528-EN-121011
Quick start
The quick start enables a quick setup with many applications. You
can nd further information in the respective chapters of the operating
instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should
protrude > 10 mm into the vessel
> 500 mm
(19.69
")
ca. 10 mm
Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling
2. Note min. socket diameter depending on the socket length
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specica-
tions on the type label.
2. Connect the instrument according to the following illustration
power supply
4...20mA
active
passive
common
IS GND
5
1
/L
/N
PE
2
+
( )
(-)
67 8
Fig. 2: Connection compartment with double chamber housing with mains
voltage
For further information see chapter "Connecting to power supply".
1. Go via the indicating and adjustment module to the menu "Setup".
2. In the menu item "Medium"you select the medium of your applica-
tion, for example "Aqueous solution".
3. Select in the menu item "Application" the vessel, the application
and the vessel form, for example, storage tank.
Mounting
Connect electrically
Set parameters