3 Planning instructions for isolating systems
Chemical seal CSB • for VEGADIF 65
36133-EN-130417
Filling oil Permissible
product temper-
atures
Permissible
product tem-
peratures at
0.05 bar
abs
< p
< 1 bar
abs
Densi-
ty in g/
cm³
Vis-
cosity
in m
2
/
s•10
-6
Expan-
sion
coe-
cient 1/K
Cor-
rective
factor
for TK
Application
area
Halocarbon oil
KN21(BAM
tested)
-40…+150°C(-
40 … +302 °F)
-40…+80°C(-
40 … +176 °F)
1.968
up to
20 °C
14
up to
20 °C
0.00086 0.83 For oxygen
and chlorine
applications
Med. white oil
KN92(FDA
approved)
-10 … +250 °C
(+14…+482°F)
-10 … +160 °C
(+14…+320°F)
0.85
up to
20 °C
5.6
up to
40 °C
0.00065 0.63 suitable for
foodstus
TheimplementedllingoilalsoinuencestheTK
zeropoint
,thepermis-
sible ambient temperature and the step response time of a chemical
seal. See also chapter "
Inuenceofthetemperaturetothezeropoint"
and "Step response time".
Thedierentialpressuretransmitteralsoinuencesthetemperature
applicationrange,theTK
zeropoint
and the step response time of the iso-
latingsystemthroughthevolumeofitslateralangesanditscontrol
volume.
1)
3.2 Inuenceoftemperaturechanges
Thellingoilexpandsasthetemperatureincreases.Theadditional
volumepressesonthechemicalseal.Themorerigidthediaphragm,
the more it counteracts a volume change. The additional volume also
adds to the process pressure on the measuring cell and thus shifts
thezeropoint.Therespectivetemperaturecoecient"TK
Process
" is
listed in chapter "Dimensions and weights".
Thefollowingdiagramshowsthetemperaturecoecientdepending
on the capillary length. The process temperature corresponds to the
calibrationtemperature.Thetemperaturecoecientsdetermined
from the diagram apply to silicone oil and the diaphragm material
316L.Forotherllingoil,thesetemperaturecoecientshavetobe
multipliedwiththecorrectionfactorfortheTKoftherespectivelling
oil.
Dierentialpressure
transmitter
Inuenceofthetempera-
ture to the zero point
1)
The control volume is the volume that must be shifted in order to utilise the
complete measuring range.