ST700 GENERAL HANDBOOK
667/HB/27880/000 Page 94 Issue 8
Serial Numbers
If the power to the controller needs to be switched off in order to fix/clear the fault(s),
then take this opportunity to record the board issues and serial numbers of the
ST700 PCBs. Record the issue states and serial numbers of the main processor
PCB and Phase Driver PCB.
Controller Checks After Clearing Fault
Is the green heartbeat LED on and beating?
Is the red system error LED off?
Is the lamp monitor learnt? (i.e. „KML:Complete‟)
Is the time/date set-up correctly?
Use „LOG‟ to look back through the historic rolling log and record the last few events.
Press „SP‟ (space) and then the „+‟ key to view the latest few records:
Record any relevant information in the controller‟s log book and record below the
date, time and reason for the previous visit as described in the log book: