Condenser Overheat Folder
Shutdown Temperature Delay
Thermostat Probe Calibration
Return NRC-100 Default settings
NOTE: Not Cabinet Settings
*) Calibration according to factory test run.
**) Gas Defrost = 1
***) Gas defrost = 0
****) Gas defrost = 15
Technical Specification
Total Power Input (W)
(Thermal Heat Rejection)
* For cabinets with 2 compressors fitted there is a 20 second delay between compressor starts so the start current of 20A is not exceeded.
The suction pressure as per climate class 3 (see below) is between -8 and -10 ºC approximately 3.5 bar, with a discharge temperature of +40 ºC (clean condenser)
approximately 17.3 bar.
The cases are designed to work in an ambient temperature not exceeding 25 degrees centigrade (C) with a relative humidity not exceeding 60% (RH) Climate Class 3.
The frontal airflow should be < 0,2m/s
Probes
The probes used are PT-1000 with rating at 0º C of 1000 Ohms. There is not a temperature range but the resistance value is approximately 950 Ohms at - 10º C and 1200
at + 50º C.