2
Specication Features
LumaWatt Energy
Management Server
(RF-EM1) . . . . . . . . . . . . .
. . . . . . .
. . . . . . . . . . Router
(RF-ROUT1)
. . . . . . . . Sensor Module
(Specify Sensor with Luminaire)
. . . . .
Gateway
(RF-GW1) . . . . .
. . . . . . .
. . . . . . . . . .
The LumaWatt System is best described as a peer-to-peer wireless network of luminaire integrated sensors that operate in accordance to programmable proles.
Proles dictate how the individual sensor operates a luminaire as well as how to function among its network peers. The end user can create and manage sensor proles
with browser-based management software and broadcast to sensors as necessary, via wireless gateways. The sensor operates in accordance to its latest loaded prole
regardless of network availability. Each sensor is capable of motion and photo sensing, metering power consumption and wireless communication.
Features
The LumaWatt software resides on the locally installed LumaWatt energy
management server. The LumaWatt software can be accessed via a web portal by
providing remote access with web browser capable devices. Sensor operation is
monitored and reported, verifying and documenting luminaire performance. Power
is metered, in real-time, to 2% accuracy. System reliability is enhanced by failure
detection and notication.
The LumaWatt energy management server is scalable addressing up to ten
gateways, each of which can address an additional 300 sensors, up to a total
system capacity of 1,000 sensors per LumaWatt energy management server
server.
The router connects to the server and powers gateways through 48V PoE
(power-over-ethernet) connections using CAT5 cable. Gateways communicate
to sensors at a radio frequency of 2405-2480 MHz using 128-bit AES encryption
security. Sensors and gateways can communicate when within 300', line-of-site of
each other, without obstructions.
Factory installed radio frequency sensors control luminaire output ON/OFF or dim in
5% increments. Sensors can be congured for up to nine events daily, based on a
combination of astronomical clock, photo sensing, or motion detection. Operational
modes dene ramp-up times, length of operation on occupancy detection,
sensitivity to motion and ambient light, including dimming level for each event.
The LumaWatt System is designed to minimize installation and commissioning
time. Luminaire commissioning data is discovered and analyzed by the LumaWatt
software to prepare for geographic location of luminaire control icons on site plans.
Verifying site plan icon locations is as easy as ashing light onto a specic sensor
in the eld. Flashing a sensor highlights the corresponding LumaWatt energy
management server screen icon for drag-and-drop positioning on the site plan.
Hardware self-diagnostics assist in troubleshooting network issues.
Optional Enclosure
An optional enclosure houses the LumaWatt energy management server and up to
two routers for installation convenience.
Warranty
Five-year limited warranty.
CAT5 Cable