ELECTRICAL DATA - 850 RPM MODELS 60Hz
- 5 -
M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)
ELECTRICAL DATA - 850 (700) RPM MODELS 50Hz
M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)
NO.
OF
FANS
208-230/1/60* 208-230/3/60 460/3/60 575/3/60
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP
1 3.4 4.3 15 5.9 7.4 15 2.9 3.6 15 2.3 2.9 15
2 6.8 7.7 15 11.8 13.3 20 5.8 6.5 15 4.6 5.2 15
3 10.2 11.1 15 17.7 19.2 25 8.7 9.4 15 6.9 7.5 15
4 13.6 14.5 20 23.6 25.1 30 11.6 12.3 15 9.2 9.8 15
5 N/A N/A N/A 29.5 35.1 40 14.5 15.2 20 11.5 12.1 15
6 20.4 21.3 30 35.4 36.9 45 17.4 18.1 25 13.8 14.4 20
8 NA NA NA 47.2 48.7 60 23.2 23.9 30 18.4 19.0 25
10 NA NA NA 59 60.5 70 29 29.7 40 23 23.6 30
12 NA NA NA 70.8 72.3 80 34.8 35.5 45 27.6 28.2 40
NO.
OF
FANS
200-220/1/50 200-220/3/50* 380-400/3/50
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP TOTAL FLA MCA MOP
1 3.6 4.5 15 6.5 8.1 15 2.7 3.4 15
2 7.2 8.1 15 13 14.6 20 5.4 6.1 15
3 10.8 11.7 15 19.5 21.1 25 8.1 8.8 15
4 14.4 15.3 20 26 27.6 40 10.8 11.5 15
5 N/A N/A N/A 32.5 34.1 40 13.5 15.1 20
6 21.6 22.5 30 39 40.6 45 16.2 16.9 20
8 NA NA NA 52 53.6 60 21.6 22.3 30
10 NA NA NA 65 66.6 80 27 27.7 40
12 NA NA NA 78 79.6 90 32.4 33.1 45
*
Not available on 4 and 5 fan single row models
and 6 fan models 183” and longer.
*
Not available on 4 and 5 fan single row models
and 6 fan models 183” and longer.