- 28 -
WORKSHEETS - SAMPLE SELECTION #1
Preliminary Data Given:
1. Evaporating temp = -20
o
F
2. Condensing temp = 105
o
F
3. Compressor capacity = 300,000 Btuh
4. Design ambient = 90
o
F
Use WORKSHEET - SINGLE CIRCUIT (P 26) to complete selection of condenser
Above selection using condenser model BVC1A23067 ensures condensing temperature will be at 105
o
F or below during
design ambient conditions. See SAMPLE SELECTION # 2 for multiple circuit selections.
1. SYSTEM DATA REQUIREMENTS
EVAP TEMP =
o
F COND TEMP=
o
F
COMPR. CAPACITY= Btuh / 1000 = MBH
COND. DESIGN AMBIENT TEMP= (AT )
o
F TD= (Cond. Temp. - Ambient Temp)
COMPRESSOR TYPE= OPEN HERMETIC (Refrigerant cooled)
REFRIGERANT= R REF. FACTOR= (see P. 2)
ALTITUDE= AT SEA LEVEL or FEET ALT. FACTOR=
(See P.2)
2. THR (Total Heat of Rejection) CALCULATION
COMPR. CAPACITY (MBH) X HR f X ALT f X REF f = THR (MBH)
X X X =
3. CONDENSER MODEL SELECTION
For the model selected
record the THR PER 1
o
F TD value = (B) (see P. 2)
4. ACTUAL CONDENSING TEMP CALCULATION
THR (from sec. 2) / value (B) = ATD (actual Temperature Difference)
/ =
To find the Actual Condensing Temp. (ACT) just add the Actual Temperature Difference (ATD)
to the design Ambient Temperature (AT).
ATD + AT = ACT
+ =
o
F
JOB REF:
COND. MODEL #
TC 1500
-20
105
300,000
300
90
15
22 1
1
300 1.55
1
465
BVC1A23067
32.165
465
32.165
14.5
O
F
14.5
90
104.5
1