Ut Output Menu
C
trL Control Mode
1SP Single set point.
2SP Two fully independent set points.
SPAL Single set point and alarm.
1
SP SP1, Set Point 1, Reverse or Direct Acting
D
IR Direct. Relay turns on with increasing pressure.
R
EV Reverse. Relay turns on with decreasing pressure.
DEL1 SP1, Set Point 1, Time Delay
Sets the amount of time a set point condition must be continuously met before the set point condition
is recognized. The DEL1 delay is adjustable from 0-60 seconds.
L
Ed1 SP1, Set Point 1, Lamp
OFF The SP1 LED on the front panel turns OFF when the SP1 relay turns OFF.
The SP1 LED on the front panel turns ON when the SP1 relay turns ON.
ON The SP1 LED on the front panel turns ON when the SP1 relay turns OFF.
The SP1 LED on the front panel turns OFF when the SP1 relay turns ON.
The following SP2 function values are only activated when CtrL is set to 2SP:
2SP SP2, Set Point 2, Reverse or Direct Acting
DIR Direct. Relay turns on with increasing pressure.
REV Reverse. Relay turns on with decreasing pressure.
DEL2 SP2, Set Point 2, time delay
Sets the amount of time a set point condition must be continuously met before the set point
condition is recognized. The DEL2 delay is adjustable from 0-60 seconds.
LEd2 SP2, Set Point 2, Lamp
OFF The SP2 LED on the front panel turns OFF when the SP2 relay turns OFF.
The SP2 LED on the front panel turns ON when the SP2 relay turns ON.
ON The SP2 LED on the front panel turns ON when the SP2 relay turns OFF.
The SP2 LED on the front panel turns OFF when the SP2 relay turns ON.
LdL9 Relay Alternation (See page 8)
OFF There is no alternating function.
ON Relays will alternate with set points SP1H/L and SP2H/L with every cycle of set
points. 2SP control mode only.