120V ac FLEX I/O 8 Input Module
(Cat. No. 1794IA8)
Installation Instructions
4
1
3
2
5
6
7
Module
Installation
This module mounts on a 1794 terminal base unit.
1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position
8
as required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left
to connect with the neighboring terminal base/adapter. You cannot
install the module unless the connector is fully extended.
3. Make sure that the pins on the bottom of the module are straight so
they will align properly with the connector in the terminal base unit.
4. Position the module (4) with its alignment bar (5) aligned with the
groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism (7) is locked into
the module.
6. Repeat the above steps to install the next module in its terminal base
unit.
!
ATTENTION: This module does not support
complementary I/O. It uses both the input and output image
tables since it is a combination input and output module.