Dil ID: 13
Dil Adı: romaina
Dil Kodu: ro5tayfun Produsele mărcii Pilz
Dünyanın En Büyük
Elektronik Bilgi Kütüphanesi



Commissioning
Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02
30
Spring-loaded terminals:
} Minimum conductor cross section on field connection terminals = 0.2 mm
2
(AWG24),
} Maximum conductor cross section on field connection terminals = 2.5 mm
2
(AWG12),
} Terminal points per connection: 2,
} Stripping length: 9 mm.
Terminals
The plug-in terminals for the inputs and outputs are not supplied with the system. You can
select between spring-loaded terminals and a screw connection.
Terminal configuration
Module supply Terminal configuration X4
4-pin female connec-
tor
1 +24 V infeed for module supply
12
34
2 0 V infeed for module supply
3 Not connected
4 Functional earth
Terminal configuration
Interfaces
The following minimum requirements must be met:
} Ethernet standards (min. Category 5) 100BaseTX
} Double-shielded twisted pair cable for industrial Ethernet use
} Shielded RJ45 connectors (industrial connectors)
CANopen interface
The connection to CANopen is made via a male 9-pin D-Sub connector.
1 n.c. 6 n.c.
1
5
6
9
. . .
. .
2 CAN_L 7 CAN_H
3 CAN_GND 8 n.c.
4 n.c. 9 n.c.
5 CAN_SHLD
n.c. = not connected
Please note the following when connecting to CANopen:
} Only use metal plugs or metallised plastic plugs
} Twisted pair, screened cable must be used to connect the interfaces
6.2.2
6.3
6.4